Standard Features:
- Motor load transfer 
controls (in-phase monitor) to keep motors operating during transfer.
 - Pre-transfer & 
post-transfer load disconnect contacts for signaling motor starters, elevators, 
VFDs and other selected loads.
 - Standard Engine Exerciser 
for weekly automatic testing of engine generator set with or without load.
 - Selectable control 
switches for voltage, frequency, time delay settings & additional control 
features.
 - Switch position lights, 
source availability lights, test switch and time delay bypass switch.\
Standard Selectable Features 
 
	- 
	In-phase monitor to transfer motor loads, without any intentional off time 
	to prevent motor inrush currents from exceeding normal starting levels.
	 
	 
	
 
	- 
	Engine exerciser to automatically test backup generator each week. Includes 
	control switch for testing with or without load.
	  
 
	- 
	Selective load disconnect, double-throw contact to operate at an adjustable 
	0 to 20 second time delay prior to transfer and reset 0 to 20 seconds after 
	transfer.   
 
	- 60 Hz or 50 Hz 
	selector switch.   
 
	- 
	
	Three-phase/single-phase selector switch.
 
 
Voltage & Frequency Sensing 
 
	- 
	Adjustable three-phase, close differential 
	voltage sensing on normal source.
	
	
 
	- 
	Normal source pickup voltage is adjustable to 
	95% of nominal; drop-out is adjustable from 70 to 90% of nominal.  
 
	- 
	Frequency sensing on emergency source. Pickup at 
	95% and dropout at 85% of nominal.  
 
 
Time Delays 
 
	- 
	Adjustable time delay to override momentary 
	normal source outages to delay all transfer switch and engine-starting 
	signals.
	 
 
	- 
	Transfer to emergency time delay. Adjustable 
	from 0 to 5 minutes for controlled timing of load transfer to emergency.
	 
 
	- 
	Retransfer to normal time delay. Adjustable to 
	30 minutes.
	
	
 
	- 
	Five-minute unloaded running 
	time delay for emergency engine generator cool down. 
 
	- 
	Four-second time delay to override momentary to 
	ignore momentary voltage and frequency transients during initial genset 
	loading.
	 
	
 
 
Standard Control Contacts
	- Switch position indicating contacts (rated 
	10 amps 250VAC, 32VDC). (1) for Normal position, (1) for Emergency position.
     
	
	- Gold plated engine start contacts (rated 5 
	amps 28VDC or 120VAC)
  
	
	Remote Control Features
	 
	
	
	Terminal provisions for connecting:  
		
		
		
		Remote contact for test or for peak 
		shaving applications. Circuit will be automatically bypassed if 
		emergency source fails. 
		
		Inhibit transfer to emergency. 
		
		
		Remote time-delay bypass switch.
		
	
	
	
	
 |