		ASCO Automatic Transfer Switch Series Feature Comparison | 
	||||
| 
		 Feature Comparison  | 
		185 | 300 | 4000 | 7000 | 
		![]()  | 
		
		 
		  | 
		
		![]()  | 
		
		![]()  | 
	|
| 
		 
			Intended Application 
		 | 
		
		 
			Residential 
		Light Commercial  | 
		
		 
			Commercial 
		Light Industrial  | 
		
		 
			Industrial 
		 | 
		
		 
			Mission Critical 
		Critical Power  | 
	
| 
		 
			Ampere sizes 
			available 
		 | 
		
		 
			100, 200, 230 
		 | 
		
		 
			30 - 3,000 
		 | 
		
		 
			30 - 4,000 
		 | 
		
		 
			30 - 4,000 
		 | 
	
| 
		 
			Low Voltage 
		 | 
		
		 
			220 - 240V 
		 | 
		
		 
			115 - 600V 
		 | 
		
		 
			115 - 600V 
		 | 
		
		 
			115 - 600V 
		 | 
	
| 
		 
			Medium Voltage 
		 | 
		
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			5kV, 15kV 
		 | 
	
| Product Type | 185 | 300 | 4000 | 7000 | 
| Open Transition Transfer Switch | 
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| Service Entrance Rated Transfer Switch | 
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| Power Transfer Load Center | 
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			N/A 
		 | 
		
		 
			Yes 
		 | 
	
| Closed-Transition Transfer Switch | 
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| Delayed-Transition Transfer Switch | 
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| Soft Load Transfer | 
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			Yes 
		 | 
	
| Bypass-Isolation transfer Switch | 
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			Yes 
		 | 
	
| Closed-Transition Bypass-Isolation TS | 
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			Yes 
		 | 
	
| Delayed-Transition Bypass-Isolation TS | 
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			Yes 
		 | 
	
| Soft Load Bypass-Isolation TS | 
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			Yes 
		 | 
	
| Withstand and Close-On Ratings | 185 | 300 | 4000 | 7000 | 
| 
		 
			WCR when used with any 
			circuit breaker 
		 | 
		
		 
			10kA 
		 | 
		
		 
			N/A 
		 | 
		
		 
			10-100kA 
		 | 
		
		 
			10-100kA 
		 | 
	
| 
		 
			WCR when used with 
			specific circuit breakers 
		 | 
		
		 
			10kA 
		 | 
		
		 
			22-100kA 
		 | 
		
		 
			22-100kA 
		 | 
		
		 
			22-100kA 
		 | 
	
| 
		 
			WCR when used with 
			current limiting fuses 
		 | 
		
		 
			100-200kA 
		 | 
		
		 
			100-200kA 
		 | 
		
		 
			100-200kA 
		 | 
		
		 
			100-200kA 
		 | 
	
| 
		 
			Withstand Short Time 
			Rating 
		 | 
		
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			36-65kA 
		 | 
		
		 
			36-65kA 
		 | 
	
| Neutral Configuration | 185 | 300 | 4000 | 7000 | 
| 
		 
			Solid 
		 | 
		
		 
			Std. 
		 | 
		
		 
			Std. 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| 
		 
			Switched 
		 | 
		
		 
			N/A 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| 
		 
			Overlapped 
		 | 
		
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			Yes 
		 | 
	
| Voltage and Frequency Settings | 185 | 300 | 4000 | 7000 | 
| 
		 
			Phase Selection 
		 | 
		
		 
			Single Phase 
		 | 
		
		 
			Single or Three Phase 
		 | 
		
		 
			Single or Three Phase 
		 | 
		
		 
			Single or Three Phase 
		 | 
	
| 
		 
			Pick up Normal Source 
			Voltage 
		 | 
		
		 
			204 Volts 
		 | 
		
		 
			90% or 95% 
		 | 
		
		 
			85 to 100% 
		 | 
		
		 
			85 to 100% 
		 | 
	
| 
		 
			Drop out Normal Source 
			Voltage 
		 | 
		
		 
			180 Volts 
		 | 
		
		 
			70% to 90% 
		 | 
		
		 
			70 to 98% 
		 | 
		
		 
			70 to 98% 
		 | 
	
| 
		 
			Pick up Emergency Source 
			Voltage 
		 | 
		
		 
			204 Volts 
		 | 
		
		 
			90% Fixed 
		 | 
		
		 
			85 to 100% 
		 | 
		
		 
			85 to 100% 
		 | 
	
| 
		 
			Drop out Emergency 
			Source Voltage 
		 | 
		
		 
			180 Volts 
		 | 
		
		 
			75% Fixed 
		 | 
		
		 
			70 to 98% 
		 | 
		
		 
			70 to 98% 
		 | 
	
| 
		 
			Frequency 
		 | 
		
		 
			60Hz 
		 | 
		
		 
			50 or 60 Hz 
		 | 
		
		 
			50 or 60 Hz 
		 | 
		
		 
			50 or 60 Hz 
		 | 
	
| 
		 
			Pick up Emergency Source 
			Frequency 
		 | 
		
		 
			57Hz 
		 | 
		
		 
			95% Fixed 
		 | 
		
		 
			90 to 100% 
		 | 
		
		 
			90 to 100% 
		 | 
	
| 
		 
			Drop out Emergency 
			Source Frequency 
		 | 
		
		 
			54Hz 
		 | 
		
		 
			85% Fixed 
		 | 
		
		 
			85 to 98% 
		 | 
		
		 
			85 to 98% 
		 | 
	
| 
		 
			Normal Over Voltage Trip 
		 | 
		
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			102 to 115% 
		 | 
		
		 
			102 to 115% 
		 | 
	
| 
		 
			Emergency Over Voltage 
			Trip 
		 | 
		
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			102 to 115% 
		 | 
		
		 
			102 to 115% 
		 | 
	
| 
		 
			Normal Over Frequency 
			Trip 
		 | 
		
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			102 to 115% 
		 | 
		
		 
			102 to 115% 
		 | 
	
| 
		 
			Emergency Over Frequency 
			Trip 
		 | 
		
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			102 to 115% 
		 | 
		
		 
			102 to 115% 
		 | 
	
| 
		 
			Pick up Normal Source 
			Frequency 
		 | 
		
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			90 to 100% 
		 | 
		
		 
			90 to 100% 
		 | 
	
| Drop out Normal Source Frequency | 
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			85 to 98% 
		 | 
		
		 
			85 to 98% 
		 | 
	
| Normal & Emergency Voltage Unbalance | 
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| Time Delay Settings | 185 | 300 | 4000 | 7000 | 
| Override Normal Source Momentary Outage | 
		 
			3 Seconds 
		 | 
		
		 
			1 or 3 Seconds 
		 | 
		
		 
			0 to 6 Seconds 
		 | 
		
		 
			0 to 6 Seconds 
		 | 
	
| Transfer to Emergency | 
		 
			15 Seconds 
		 | 
		
		 
			0 or 5 Minutes 
		 | 
		
		 
			0 to 60 Minutes 
		 | 
		
		 
			0 to 60 Minutes 
		 | 
	
| Re-transfer to Normal Utility Power Loss Mode | 
		 
			5 Minutes 
		 | 
		
		 
			1 Sec. to 30 Mins. 
		 | 
		
		 
			0 to 60 Minutes 
		 | 
		
		 
			0 to 60 Minutes 
		 | 
	
| Engine Cool Down | 
		 
			1 Minute 
		 | 
		
		 
			5 Minutes 
		 | 
		
		 
			0 to 60 Minutes 
		 | 
		
		 
			0 to 60 Minutes 
		 | 
	
| Override Emergency Source Momentary Outage | 
		 
			15 Seconds 
		 | 
		
		 
			4 Seconds 
		 | 
		
		 
			0 to 60 Minutes 
		 | 
		
		 
			0 to 60 Minutes 
		 | 
	
| Emergency Exerciser | 
		 
			14 Day 
		 | 
		
		 
			7 Day 
		 | 
		
		 
			Programmable 
		 | 
		
		 
			Programmable 
		 | 
	
| Indication and Controls | 165 | 300 | 4000 | 7000 | 
| Load Connected to Normal | 
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| Load Connected to Emergency | 
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| Normal Source Available | 
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| Emergency Source Available | 
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| Transfer Test Switch | 
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| Terminals for Remote Transfer Control | 
		 
			N/A 
		 | 
		
		 
			Std. 
		 | 
		
		 
			Std. 
		 | 
		
		 
			Std. 
		 | 
	
| By-pass Time Delay | 
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| Transfer Inhibit | 
		 
			N/A 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| In-Phase Monitor | 
		 
			N/A 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| Load Disconnect Contacts with Time Delay | 
		 
			N/A 
		 | 
		
		 
			Std. 
		 | 
		
		 
			Optional 
		 | 
		
		 
			Optional 
		 | 
	
| Event Log | 
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| Power Manager | 
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			Optional 
		 | 
		
		 
			Optional 
		 | 
	
| Transfer Controls Lock Out | 
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Optional 
		 | 
	
| Enclosures | 185 | 300 | 4000 | 7000 | 
| Type 1 | 
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| Type 3R | 
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| Type 4 | 
		 
			N/A 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| Type 4X | 
		 
			N/A 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| Type 12 | 
		 
			N/A 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| Connectivity | 185 | 300 | 4000 | 7000 | 
| RS-485 Serial | 
		 
			N/A 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| Ethernet | 
		 
			N/A 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| 
		 
			Modbus® 
		 | 
		
		 
			N/A 
		 | 
		
		 
			N/A 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| 
		 
			Monitoring and Control 
			via ASCO® 
			Products 
		 | 
		
		 
			N/A 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
		
		 
			Yes 
		 | 
	
| Accessories | 185 | 300 | 4000 | 7000 | 
| 
		 
			Optional Accessories 
		 | 
		
		 
			Limited 
		 | 
		
		 
			Limited 
		 | 
		
		 
			Limited 
		 | 
		
		 
			Extensive 
		 | 
	