AIR CONDITIONING & HEAT PUMP LOADS - TYPICAL

SIZE BTU HP Running Load Starting Load
Running
kW
Amps @
240 Volts 1 Phase
Amps @
208 Volts 3 Phase
Amps @
480 Volts 3 Phase
Starting
kW
Amps @
240 Volts 1 Phase
Amps @
208 Volts 3 Phase
Amps @
480 Volts 3 Phase
1 Ton 12,000 1 1 5 3 1 3 25 17 7
2 Ton 24,000 2 2 10 7 3 6 50 33 14
3 Ton 36,000 3 3 15 10 4 9 75 50 22
4 Ton 48,000 4 4 20 13 6 12 100 67 29
5 Ton 60,000 5 5 25 16 7 15 125 83 36
7.5 Ton 85,000 7.5 7.5 37 24 11 17 188 125 54
10 Ton 120,000 5 (x2) 10 49 33 14 15 125 83 36
10 Ton 120,000 10 10 49 33 14 20 188 167 72
15 Ton 180,000 7.5 (x2) 15 74 49 21 17 125 125 54
15 Ton 180,000 15 15 74 49 21 30 250 250 108
20 Ton 240,000 10 (x2) 15 98 65 28 20 188 167 72
20 Ton 240,000 20 20 n/a 65 28 40 500 333 144
25 Ton 300,000 25 25 n/a 82 35 50 625 416 180
30 Ton 360,000 15 (x2) 30 n/a 98 42 30 375 250 108
30 Ton 360,000 30 30 n/a 98 42 60 750 500 217
40 Ton 480,000 20 (x2) 40 n/a 131 57 40 500 333 144
40 Ton 480,000 40 40 n/a 131 57 80 1000 666 289
50 Ton 480,000 25 (x2) 50 n/a 163 71 50 625 416 180
50 Ton 480,000 50 50 n/a 163 71 100 1250 833 361
 