ASCO Standard Features and Diagram  -  Series 7000 Service Entrance**

Standard Features
  • Available from 150 to 4000 amperes
  • ASCO 7000 Series Power Transfer Switch, UL 1008 Listed
  • Standard UL Type 1 enclosure
  • Disconnect and over current protective device on the utility source: molded case circuit breaker 150 to 800 Amp; insulated case 1000 to 4000 Amp
  • Disconnect link on Neutral
  • Disconnect link on Ground
  • Ground and Neutral bus, all silver-plated copper
  • Solderless screw type terminals for external power connections
  • Labeled UL 891, meets all NEC requirements for service entrance
  • Internet enabled command and control available with optional ASCO SiteWebTM
  • Ground fault circuit protection on utility breaker when required by NEC
7000 Series Wiring Graphic
One line diagram of a typical service entrance rated transfer switch available in Solid, Switched or Overlapping Neutral.

opyright © 1996-2016 GeneratorJoe Inc. & GeneratorJoe®. All Rights Reserved. -  © Copyright 1996-2016 ASCO Power Technologies