GeneratorJoe, Industrial Generator, 550 kW, (688 kVA) 60 Hz,, diesel fueled, liquid cooled, three phase, Model 550 CP3

pixie PowerPixie™
generatorjoe GeneratorJoe™

Industrial Generator, GeneratorJoe, Centurion "P"™ Series, 550 kW (688 kVA) 60 Hz, or 458.3 kW (573.3 kVA) 50 Hz. SKU GJCP-550D321, Model 550 CP3, (Open, No Enclosure), Perkins 2506C-E15TAG4, three phase, diesel fueled, liquid cooled, 1800 RPM, electric start, auto start, Tier 3, UL2200, GeneratorJoe Generator

550 CP3, GJCP-550D321
550 CP3, GJCP-550D321

  Product Packages

Centurion "P"™ Series, 550 kW (688 kVA) 60 Hz, SKU GJCP-550D321, Model 550 CP3, Open, No Enclosure, w/260 gallon tank   Our Price Qty
Perkins 2506C-E15TAG4, three phase, diesel fueled, liquid cooled, 1800 RPM, electric start, Tier 3 1.0 DN, $64,319.49
Package Includes: Analog Control Panel, End Mount,, Base Fuel Tank, 260 Gallon, DW, UL142,  
Centurion "P"™ Series, 550 kW (688 kVA) 60 Hz, SKU GJCP-550D321, Model 550 CP3, Weather Enclosed, w/260 gallon tank   Our Price Qty
Perkins 2506C-E15TAG4, three phase, diesel fueled, liquid cooled, 1800 RPM, electric start, Tier 3 1.0 DN, $79,026.99
Package Includes: Weather Enclosure, w/silencer on top, (450-550 kW), Analog Control Panel, End Mount,, Base Fuel Tank, 260 Gallon, DW, UL142,  
Centurion "P"™ Series, 550 kW (688 kVA) 60 Hz, SKU GJCP-550D321, Model 550 CP3, Sound Enclosed, Level 1, w/260 gallon tank   Our Price Qty
Perkins 2506C-E15TAG4, three phase, diesel fueled, liquid cooled, 1800 RPM, electric start, Tier 3 1.0 DN, $78,444.49
Package Includes: Sound Enclosure, Level 1, w/silencer (450-550 kW), Analog Control Panel, End Mount,, Base Fuel Tank, 260 Gallon, DW, UL142,  
Centurion "P"™ Series, 550 kW (688 kVA) 60 Hz, or 458.3 kW (573.3 kVA) 50 Hz. SKU GJCP-550D321, Model 550 CP3, Sound Enclosed Level 2, w/260 gallon tank   Our Price Qty
Perkins 2506C-E15TAG4, three phase, diesel fueled, liquid cooled, 1800 RPM, electric start, auto start, Tier 3, UL2200 $83,029.49
Package Includes: Sound Enclosure, Level 2, w/silencer (450-550 kW), Analog Control Panel, End Mount,, Base Fuel Tank, 260 Gallon, DW, UL142,  
Centurion "P"™ Series, 550 kW (688 kVA) 60 Hz, or 458.3 kW (573.3 kVA) 50 Hz. SKU GJCP-550D321, Model 550 CP3, Typically Equipped   Our Price Qty
Perkins 2506C-E15TAG4, three phase, diesel fueled, liquid cooled, 1800 RPM, electric start, auto start, Tier 3, UL2200 $89,112.54
Package Includes: 277/480 VAC, 3 phase,, Frame 3, Breaker, 1800A. 3 Pole, 277/480V, (500 kW),, Sound Enclosure, Level 1, w/silencer (450-550 kW), DGC-2020 Control Panel, End Mount,, Base Fuel Tank, 575 Gallon, DW, UL142,, Flexible Fuel Line, Emergency Stop Switch (Remote Mount Break Glass), Block Heater ( installed, no charge), 2.5A, 24VDC, Battery Tender,, Battery, 2 each, (CP 250-600 kW), Five year/5,000 hour GenSet warranty (Standard, no charge)  

The GeneratorJoe Model 550 CP3 is a Centurion "P"™ Series generator with 550 kW (688 kVA) 60 Hz, of maximum output. These industrial generators are suitable for prime power and standby use. When you need the dependability of an industrial grade generator, with all the features you need, the Centurion "P"™ Series is for you. Available in several models, these models are competitively priced to deliver the performance and value found only on more expensive competitors models.

GeneratorJoe generators are designed for many applications where power is needed. GeneratorJoe generators are manufactured to commercial specifications using the latest manufacturing technologies. All models are built with the quality and reliability you would expect from a leading generator manufacturer.

The Newage Stamford brushless alternator used on this model is manufactured to exacting specifications using the latest mass production methods. GeneratorJoe generators use technology to control the voltage with a voltage variation less than 3% throughout the entire power range. That means you can use this generator with computers and sensitive electronics, safely, with no sacrifice in performance.

This model features a premium Perkins model 2506C-E15TAG4, 6 cylinder, 836 HP, diesel fueled, liquid cooled engine with electric start. 1.0 DN, This model runs at 1800 RPM and generates 550 kW (688 kVA) 60 Hz, or 458.3 kW (573.3 kVA) 50 Hz. of Standby (emergency or maximum) power and 495 kW 412.5 kW prime (continuous) power at a primary voltage of 277/480 VAC, three phase, 60/50 Hertz, with 0.25% voltage accuracy. Single phase models are available as 120/240 VAC. Three phase models are available as 120/240, 120/208 or 277/480 VAC. If 50 Hz models are available they would be built as a special order. For 50 Hz voltage and amperage ratings, click on the Open Specification Window and then check the 50 Hz check box.
 
This model comes with a Digital 300 control panel with autostart. If you require voltage and amperage readouts, upgrade to the Digital 400 panel.
 
This model has economical fuel use of 19.25 gallons at 1/2 load. Running time is over 5.2 hours on a typical tank. See Fuel Tanks below.
 
The price includes a factory warranty of 60 months or 5000 hours whichever comes first.

Open dimensions are 140" Long X 66" Wide X 75" High. Open weight is 8579 lbs.

Trailers: Many industrial generators may be mounted on trailers. If trailers are available as a option they will be shown in the Trailer Option Window. Rental type generators equipped with single and three phase power are generally supplied with trailers as standard equipment. To determine the right trailer to use you need to use the following formula: GenSet weight + Tank weight + Fuel weight (Diesel is 7.2 lbs. per gallon), + Other Equipment weight equals Total Payload.  Select a trailer that has a payload of at least the Total Payload or more.

Enclosures: Weather and sound proof enclosures (if available), are built using steel panels and locking doors on a modular structural base frame. Sound enclosures include a rock-wool layer of insulation, which complies with the prevailing regulations and accomplishes the sound attenuating elements. Most enclosures include hot ambient air extraction fan. Select an enclosure from the Product Options windows, if available. For additional enclosure information click on Enclosure Details in the Additional Information area below.

Fuel Tanks: Single walled (non UL) and double walled (UL) tanks are available for this model as shown in Product Options. When base tanks are added, the day tank (if installed) is removed. Tank prices include installation, fuel level gage and fuel line piping, to make a complete operable unit. You may check the running time on that tank size, by viewing the tank in the opened Specification Window or by typing in the gallons or your external tank in the box provided and clicking the arrow. Local codes on fuel tanks vary, check with your local building department and state air quality department to determine any fuel tank requirements for your area. Select the tank you need from the Product Options windows, if available. Select a tank and click "Details" for to see dimensions and other information about that tank. If you have special requirements call your GeneratorJoe sales representative.

Transfer Switches: The automatic transfer switch monitors utility and generator power. When utility power fails or is unsatisfactory, the transfer switch control starts the generator set, checks the generator speed and voltage output and transfers the load to the generator set. When utility power is restored the transfer switch automatically transfers back to utility power. The generator is allowed to cool down for a short period and then shuts down. The system instantly resets itself and is ready for the next power interruption. No action is required by the user.

You must select a transfer switch that is the same size in amps (or larger) then your building service or sub-panel. The transfer switch must also be the same size in amps (or larger) than the maximum output of the generator you select. Example: If you have a 12 kW generator operating at 120 VAC single phase, (100 Amps) and a 200 amp building service you need a 200 Amp transfer switch or you must install a 100 Amp sub-panel. Transfer switches should be installed by a licensed electrician. For more information on transfer switches please see About Transfer Switches.

Select a transfer switch to go with your generator from the drop down option list at the top of this page under Product Options. The transfer switches shown are compatible with this generator. If you need additional transfer switch poles, auxiliary contacts or communications features, ASCO Transfer Switches. For special needs, volume purchases and other questions, call your GeneratorJoe sales representative at 707 539-9003 for assistance. All ASCO switches are shipped FREE when you purchase the switch with a generator.

Other Requirements or Options: If you do not find the options you need in the drop down option windows above or if you have other requirements, please call us and tell us what you require. If your needed option is not available we have many other brands that may provide the options you need or we will have a generator custom made if necessary. Please contact us at (707) 539-9003 or write sales@generatorjoe.net.

CLICK> Open Specification Window on the blue bar immediately above to see detailed specifications on this product. A window will fold down.
In the opened specification window you can find conversions for metric measurements, single phase deration of three phase units, derating calculations for elevation and temperature as well as fuel consumption and total run time by tank size. Click the Open Specification Window button to see these utilities and additional information.
Accessories available for this model are shown in Product Options above. Select an option in the drop down windows and the price will be recalculated automatically.
Additional Information on this product is available on buttons and links at the bottom of this page.
Transfer Switches shown on in Product Options (above) are matched to this generator. For details about transfer switches go to the Additional Information below.

Please see our extensive educational area on the left side blue column of this screen under the Information sign.

Included Equipment: Generator Perkins diesel engine and medium duty alternator on a heavy duty steel frame skid base, standard control panel interface with autostart (customer selects panel), automatic shutdowns, radiator, water jacket (block heater), vibration isolators, air filter, oil drain kit with extention, battery rack, battery hold down and cables, owners manual and warranty. Batteries are not included. Other options are NOT included please purchase the options from the option lists.

Standard Features
Centurion "P"™ Series, 550 kW (688 kVA) 60 Hz, or 458.3 kW (573.3 kVA) 50 Hz. SKU GJCP-550D321, Model 550 CP3, (Open, No Enclosure)
Insulation class H/H
Skid mounted with vibration isolatersBattery cables and rackHeavy duty fabricated steel base frame
Electronic governorWater Jacket Heater5 year, 5000 hour warranty
Options Available
Centurion "P"™ Series, 550 kW (688 kVA) 60 Hz, or 458.3 kW (573.3 kVA) 50 Hz. SKU GJCP-550D321, Model 550 CP3, (Open, No Enclosure)
Main line circuit breakerCritical silencerEnclosure or soundproof canopy
DGC-2020 Digital Control PanelSub-base fuel tank