GE Zenith, Transfer Switches Generator, ,, , Model ZTS-BOT, ZTS-BDT, ZTS-BCT, ZTS-BOT-O, ZTS-BDT-O & ZTS-BCT-O
ZTS-BOT, Automatic, 400 Amp, 3 Pole, Outdoor, Nema 3R
Our Price
Qty
$14,845.60
Package Includes: ZTS-BOT, 400 Amp, 3 Pole, Enclosed,, Enclosure, ZTS-BOT, 100 to 400 Amp, NEMA 3R
GE Zenith- ZTSCT, ZBTS, ZBTSD & ZBTSCT Series Transfer Switches - Closed Transition & Open, Closed and Delayed Transition w/ Bypass Isolation. Enclosed Only. Zenith is of the world leaders in emergency and standby power transfer solutions, Zenith keeps your power on. Zenith is committed to providing a full range of quality-driven products, backed by nationwide 24-hour service and support.
The switches in this group are designed for specific critical applications. They are utilized in industrial standard applications requiring dependability and ease of operation. These switches combine reliability, flexibility and ease of use in a rugged industrial package. All these switches work together with any remote-start generator that use two-wire control, allowing the standby power system to be fully automatic. Designed for specific applications, this Series builds on ZTS technology while providing a pre-engineered project solution.
The ZTS Series is the building block of our transfer switch product line including all the switches shown on this page. This ruggedly built power contactor family of switches has been specifically designed for transfer switch duty with dependability, versatility and user friendliness of prime concern. These special switches are available in NEMA enclosures to the customer’s specifications/
ZTSCT Closed Transition
Loads such as electronic equipment, HID lighting, motor starters and the like are sensitive to even the 30- to 100-millisecond outage experienced during a typical transfer switch operation. Therefore, testing and use of the standby system may not be optimized and necessary system checks may be omitted, because of concerns about the effects of transfer. In addition, opportunities for peak shaving and utility incentive rates may be passed over because of the inability to accept short power interruptions.
GE Zenith's proven switching technology combines with controls developed through years of experience with synchronizing switchgear to provide worry-free transfers in a closed transition mode. With GE Zenith Controls' high-speed drive system, the overlap of the normal and alternate sources is less than 100 milliseconds. When one source is not within normal limits, such as during a power outage, the ZTSCT operates in an open transition mode. Closed transition operation (no power interruption) during transfer and retransfer when sources are within specified parameters
Open transition transfer operation is initiated upon a source failure .
ZBTS Bypass-Isolation
In critical applications such as hospitals, data centers and airports, power cannot be interrupted for maintenance of automatic transfer switches. In such circumstances, a bypass-isolation switch is essential and is often required by code.This model is the solution when interruption of power during service or testing is not acceptable. Consisting of two major modules-the Automatic Transfer (ATS) and the Bypass-Isolation Switch-the ZBTS Series incorporates the rugged construction of all Ge Zenith ZTS Series automatic switches with a quick make/quick break bypass switch manual load transfer handle and the SZenith control/interlock system, which consists of both mechanical and electrical interlocks.The bypass uses normal failure sensing and a time delay to start the engine automatically if a failure occurs when the ATS has been removed for service-which can be done without disturbing the load.
ZBTSD Bypass-Isolation-Delayed Transition
The ZBTSD Series incorporates the features of the ZBTS Bypass-Isolation Switch with those of the ZTSD unit for transfer of large motor loads, transformers, uninterruptible power supplies (UPS) systems or load shedding to a neutral "off" position.In critical systems such as those of hospitals and airports, power cannot be interrupted for maintenance and testing of automatic transfer switches (ATSs). In such circumstances, a bypass-isolation switch is essential and often required by code. The GE Zenith Controls ZBTSD Series Delayed Transition Transfer/Bypass-Isolation Switch meets requirements for inspection and/or maintenance of the delayed transition transfer switch without power interruption.The ZBTSD Series incorporates the rugged construction of all GE Zenith ZTS Series switches with a quick-make/quick-break manual load transfer handle and Zenith control/interlock system, consisting of both mechanical and electrical interlocks.The bypass uses normal failure sensing and a time delay to start the engine automatically if a failure occurs when the ATS has been removed for service.
ZBTSCT Closed Transition-Bypass Isolation
The ZBTSCT Closed Transition Transfer Switch may be outfitted with a bypass-isolation switch for the utmost in reliability and versatility. The ZBTSCT Series provides the ability to withdraw the transfer switch unit for maintenance or inspection. Using the proven switching technology of the ZTS/ZTSD Series of transfer switches, combined with controls developed during GE Zenith Controls' years of experience, the ZBTSCT Series allows an overlap of normal and alternate sources of less than 100 milliseconds.When conditions are sensitive to generator voltage drop or frequency dips, GE Zenith Controls can provide a variation of the closed transition method of transfer that combines the attributes of a ZTSCT with generator paralleling switchgear. This method of transfer requires greater coordination with the utility company and, typically, more sophisticated relay protection schemes. We suggest you specify option SL on your ZBTSCT (SL) unit and consult your GeneratorJoe representative early in the project cycle to ensure proper application.
Standard Features for all ZTSCT, ZBTS, ZBTSD & ZBTSCT Series Transfer Switches
Load is not interrupted during bypass & isolation operation
Automatic transfer switch is located on a draw-out mechanism to facilitate maintenance
Emergency power systems can be electrically tested without disturbing the load
Power cables do not have to be disconnected to remove automatic transfer switch
Bypass to any available source with ATS removed
Engine start circuit maintained during bypass operation; normal power failure causes engine start contact closure even with the ATS removed
Diagnostic lights and detailed instructions for simple step-by-step operation
Mechanical and electrical interlocks ensure proper sequence of operation
Bypass switch contacts are closed only during the bypass-isolation operation
Silver-plated copper bus interconnection of the transfer and bypass switches on all sizes.
General Information:
GE Zenith’s ZTSCT, ZBTS, ZBTSD & ZBTSCT Series Transfer Switches are designed for emergency, critical and life support standby and prime power applications.
Standard models in stock, dropped shipped to your location.FREE SHIPPING when purchased with a generator!
Sizes include 40 to 4,000 amps with 2, 3 or 4 pole configurations.
Available 120/240 VAC, 120/208 VAC, 277/480 VAC and other voltages up to 600 VAC. See Factory Brochure under Additional Information.
Switch is true double throw, mechanically interlocked and mechanically held, electrically operated utilizing a reliable, field-proven single solenoid operator.
Switch mechanism absolutely prohibits connecting both sources together. Cannot be over-ridden.
Available inZTSCT (utility-generator), ZTSCTU (utility-utility), ZTSCTM (manual) configurations.
Available in NEMA Type 1 (indoor), 3R (outdoor) enclosures and open (back-panel mounted) configurations as well as NEMA 4, 4X & 12.
Dimensions shown on ZTS Dimensions under Additional Information.
GE Zenith’s ZTSCT, ZBTS, ZBTSD & ZBTSCTswitches are equipped with the MX250 control panel. This microprocessor control includes:
Under-voltage sensing (90% pickup, 80% dropout) of Source 1 (normal).
Voltage and frequency sensing of Source 2 (emergency), (90% voltage, 95% frequency pickup).
Time Delay Engine Warm-up (W) - Transfer to Emergency (Source 2) - 0 -5 minutes, factory setting 1 second.
Time Delay Utility Stabilization/Retransfer to Utility (Source 1) (T) - 0-60 minutes, factory setting 30 minutes.
Time Delay Engine Cool Down (U) - 0-60 minutes, factory setting 5 minutes.
Generator exerciser timer built-in. 365 day adjustable time setting. Factory set at 7 days. Exercises Source 2 with or without load.
Switches feature contacts that are easily accessible for easy inspection and preventive maintenance.
Rated for standby applications and intended for use only in optional (non-critical) standby systems in accordance with the National Electrical Code. NEC/NFPA 70, Article 702.
Not intended for emergency or life-support systems.
Qualified and listed to
UL 1008, CSA 22.2 and IEC, 480 VAC 50/60 Hz for automatic transfer equipment standards.
For technical data, dimensions, features, remote controls, monitoring, warranty and other information. See Additional Information below.
CALL FOR PRICING: Due to the extensive array of types, options and accessories please contact the GeneratorJoe sales department for competitive pricing. Call GeneratorJoe at 707 539-9003 or write sales@generatorjoe.net.
@@INCLUDED_EQUIPMENT@@
Standard Features
ZTS-BOT, ZTS-BDT, ZTS-BCT, ZTS-BOT-O, ZTS-BDT-O & ZTS-BCT-O, Industrial Automatic Transfer Switches with Bypass Isolation. Standard, Delayed & Closed Transition, Enclosed & Open
Available in ZTS (utility-generator), ZTSU (utility-utility), ZTSG (generator-generator) and ZTSM (manual) configurations
Close differential 3 phase under-voltage sensing of Source1 (normal) - factory standard setting 90% pickup, 80% dropout (adjustable); under-frequency sensing of Source 1 factory setting 95% pickup (adjustable).
Contact transfer speed less than 100 milliseconds
eTemperature rise test per UL 1008 conducted after overload and endurance tests in unventilated enclosure-exceeds UL requirements
High close-in and withstand capability
NEMA Type 1 enclosure is standard. Also available in NEMA 3R, 4, 4X & 12.
Voltage and frequency sensing of the Source 2 (emergency) - factory standard setting 90% pickup voltage, 95% pickup frequency (adjustable).
Indicating LEDs for source availability and switch position.
Pushbuttons for test, exerciser set, timer bypass and program cancel.
Special status annunciation of in-phase transfer and timer operation.
Selectable 7, 14, 21 or 28 day (factory set 28 dsays) generator (source2) with or without load exerciser timer.
Diagnostic LED indications in logical one-line configuration.
Close differential under-voltage sensing of the normal source.
Voltage and frequency sensing of the emergency source.
Test switch (fast test/load/no load) to simulate normal source failure - automatically bypassed should the emergency source fail .
Double throw, interlocked operation .
Electrically operated, mechanically held by a simple, over-center mechanism.
Segmented silver tungsten alloy contacts with separate arcing contacts on 600 amps and above.
Arc quenching grids, enclosed arc chambers and wide contact air gap for superior source-to-source isolation on all units.
Control circuit disconnect plug and drive inhibit switch for safe maintenance.
Components accessible for inspection and maintenance without removal of the switch or the power conductors.
Mechanical indicator and contact chamber cover designed for inspection, safety and position designation.