ASCO Power Manager - Series 7000 Service Entrance

Power Manager Sign

The ASCO Power Manager (formerly Data Monitor) is a microprocessor based metering device that provides real-time measurements of single and three phase power systems. The Power Manager uses digital signal processing technology to measure voltage and current per phase; real, reactive and apparent power, and bi-directional energy. All measurements are viewed locally with a backlit liquid crystal display and can be displayed remotely with ASCO PowerQuest® VPi or SiteWebTM products.

Direct voltage input for systems up to 600 Volts AC can be monitored without the use of external potential transformers (PT's). Measure 3 phase currents and a fourth current input is available for measuring current in the neutral conductor. The Power Manager includes one discrete input for transfer switch position, eight general purpose discrete inputs, and four relay outputs for controlling or monitoring external devices.

Power Manager Manual   381333-192A

ASCO Power Manager Panel

Power Metering
  • Voltage:
    Line - Line: VAB, VBC, VCA, VAVERAGE
    Line - Neutral: VAN, VBN, VCN, VAVERAGE
  • Frequency: 45.0 to 66.0 Hertz
  • Current: IA, IB, IC, IAVERAGE
  • Unbalance %: Voltage, Amps
  • Real Power: KWA, KWB, KWC, KWNET
  • Reactive Power: KVARA, KVARB, KVARC, KVARNET
  • Apparent Power: KVAA, KVAB, KVAC, KVANET
  • Real Energy: KWHIMPORT, KWHEXPORT, KWHNET
  • Reactive Energy: KVARHIMPORT, KVARHEXPORT, KVARHNET
  • Power Factor: PFA, PFB, PFC, PFNET

ASCO Power Metering Connection Block

Data Access

  • Eight digital inputs, four relay outputs.
  • Input/Output 15-character, user definable screen display for identification of input/output signals.

Configurable Designations

  • Local - A four line 20 character LCD backlit display.
  • Remote - With optional Acc. 72A communication module and Power Manager monitoring sy-point based on watt demand and can be used to control one of the four relay outputs. Used for peak shaving applications.

Integrated ATS Features

  • When configured on load of ATS:
    • Displays ATS position.
    • Displays power data as a function of ATS position (normal/emergency).
    • Accumulates energy data separately for normal and emergency sources.

Optional Configurations and
Connection Arrangements

Connected To:

With Display

Without display

Load

Acc. 85L

Acc. 75L

Load

Acc. 85N

Acc. 75N

Load

Acc. 85M

Acc. 75M

Load

Acc. 85R*

Acc. 75R*

Add Suffix "A" to above designations if neutral conductor monitoring is required.

NOTE: Accessory 75 and 85 include component mounting, CTs, shorting blocks and all necessary interwiring.

* Bypass & isolation switch contacts wired to discrete power manager inputs.