This is a new pop-up window on top of your GeneratorJoe browser window.  CLICK TO CLOSE WINDOW

ASCO Power Manager - Series 7000 Soft Load

Advanced Power Control and Monitoring
5200 Power Manager XP

Two Power Managers, one each dedicated to utility and onsite power sources, provide protective relay functions for reliable parallel operation of the sources in the 7000 Series Soft Load Power Transfer Switch. The power managers include digital inputs and outputs (Device 85).

In addition to directional power, a directional over-current device provides the most reliable protection against undesirable back-feeding of onsite power to the utility grid.

Power Manager Xp Manual    381333-199B

Advanced Power Control and Monitoring

Data Access

  • Eight digital inputs, four relay outputs.
  • Input/Output 15-character, user definable screen display for identification of input/output signals.

Configurable Designations

  • Local - A four line 20 character LCD backlit display.
  • Remote - With optional Acc. 72A communication module and Power Manager monitoring sy-point based on watt demand and can be used to control one of the four relay outputs. Used for peak shaving applications.

Integrated ATS Features

  • When configured on load of ATS:
    • Displays ATS position.
    • Displays power data as a function of ATS position (normal/emergency).
    • Accumulates energy data separately for normal and emergency sources.

Optional Configurations and
Connection Arrangements

Connected To:

With Display

Without display

Load

Acc. 85L

Acc. 75L

Load

Acc. 85N

Acc. 75N

Load

Acc. 85M

Acc. 75M

Load

Acc. 85R*

Acc. 75R*

Add Suffix "A" to above designations if neutral conductor monitoring is required.

NOTE: Accessory 75 and 85 include component mounting, CT's, shorting blocks and all necessary inter-wiring.

* Bypass & isolation switch contacts wired to discrete power manager inputs.

Utility Source Power Manager Utility Source Power Manager
Device 27/59 Under and over voltage Device 27/59 Under and over voltage
Device 32 Directional power Device 32 Directional power
Device 46 Negative sequence overcurrent Device 40 Loss of excitation (excess VARs)
Device 47 Negative sequence voltage Device 81 Under and over frequency
Device 67 Directional over-current Device 86 Lockout relay

Copyright © 1996-2019 GeneratorJoe Inc. & GeneratorJoe®. All Rights Reserved. -  © Copyright 1996-2016 ASCO Power Technologies