UL Listed Withstand and Close-On Ratings - Series 7000 Soft Load |
|||||||
Switch Rating ( Amps) |
UL 1008 Withstand and Close-On Ratings at 480 Volts AC |
Short Time Withstand Ratings(4) |
|||||
Transfer Switches |
Bypass Switches |
Current - Limiting Fuse Rating |
Max. Fuse Type |
Specific Breaker Rating |
"Any" Breaker(3) Rating |
||
amps |
types |
||||||
30 |
- |
100,000 |
60 |
J |
10,000 |
10,000 |
N/A |
70, 100, 150 |
- |
200,000 |
200 |
J |
22,000 |
10,000 |
N/A |
260, 400 |
150, 260, 400 |
200,000 |
600 |
J |
42,000 |
35,000 |
N/A |
600, 800, 1000, 1200 |
600, 800 |
200,000 |
1600(6) |
L |
65,000 |
65,000 |
36,000(5) |
- |
1000, 1200 |
200,000 |
2000 |
L |
85,000 |
85,000 |
65,000 |
1600, 2000(7) |
1600, 2000 |
200,000 |
3000 |
L |
100,000 |
100,000 |
65,000 |
3000 |
3000 |
200,000 |
4000 |
L |
100,000 |
100,000 |
65,000 |
4000 |
4000 |
200,000 |
6000 |
L |
100,000 |
100,000 |
65,000 |
Notes:
|
Ordering Codes - ASCO Series 7000 Soft Load |
|||||||||||||
To order an ASCO Series 7000 Soft Load Transfer Switch, complete the following catalog number: | |||||||||||||
7 + A + SLS + A + 3 + 400 + N + 5X + C | |||||||||||||
Product | Neutral Code* | Phase Poles | Amperes |
Voltage Code |
Options |
Cabinet |
|||||||
7 |
A |
Automatic |
SLS SLB |
Soft Load Closed-Transition Soft Load W/Bypass-Isolation Switch |
--- A C D |
No Neutral Solid Neutral Switched Neutral Overlapping Neutral |
3 |
150 |
C |
208 |
5X Optional accessories
|
C |
Type 1 enclosure |
220 |
D | 220 |
H |
Type 3R secure enclosure |
|||||||||
400 |
E | 230 | |||||||||||
240 |
F | 240 | |||||||||||
800 |
L | 440 | |||||||||||
1000 |
M | 460 | |||||||||||
1200 |
N | 480 | |||||||||||
1600 |
P | 550 | |||||||||||
2000 |
Q | 575 | |||||||||||
3000 |
R | 600 | |||||||||||
4000 | |||||||||||||
Notes:
|
This is a new pop-up window on top of your GeneratorJoe browser window. CLICK TO CLOSE WINDOW